Gartner spells out route to datacentre efficiency

Save money, save the planet

By Tom Jowitt




Analyst Gartner has launched a list of best practises in the datacentre, designed to save electricity and improve cooling.

Gartner says that in a conventional datacentre, between 35 and 50 percent of the electricity consumed is for cooling compared to only 15 percent in best practise or ‘green' datacentres.

"Virtually all datacentres waste enormous amounts of electricity using inefficient cooling designs and systems," said Paul McGuckin, research vice president at Gartner in a statement. "Even in a small datacentre, this wasted electricity amounts to more than 1 million kilowatt hours annually that could be saved with the implementation of some best practices."

The main reason for the waste in conventional datacentre cooling is the "unconstrained mixing of cold supply air with hot exhaust air."

"This mixing increases the load on the cooling system and energy used to provide that cooling, and reduces the efficiency of the cooling system by reducing the delta-T (the difference between the hot return temperatures and the cold supply temperature). A high delta-T is a principle in cooling," McGuckin said.

Gartner's eleven top tips for reducing power consumption are:

  • Plug holes in raised floor. This point was also raised by SunGard Availability Services last month, as apparently holes in the floor allows cold air to escape and mix with hot air. This single low-tech retrofit can save as much as 10 percent of energy used for datacentre cooling, says Gartner.
  • Installing blanking panels. Datacentres are full of racks, and unused rack space needs to be covered with a blanking panel so that airflow can be properly managed, for example by preventing hot air leaving equipment in one section of the rack and then entering the cold air intake for other equipment elsewhere in the rack. Gartner says when these panels are used effectively; supply air temperatures can be lowered by as much as 22 degrees Fahrenheit (or minus 5 degrees Celsius).
  • Co-ordinate CRAC units. A CRAC unit (according to Gartner) is an older Computer Room Air-conditioning Unit (CRAC). Apparently these units operate independently of each other when cooling and dehumidifying the air. Gartner suggests that if these units could be tied together with newer technologies, and their efforts co-ordinated, then the results would be a much more efficient cooling system.
  • Improve underfloor airflow. This typically affects older datacentres, where the space under the raised flooring is a lot more constrained than newer builds. Many old datacentres also use the underfloor spacing for running data and power cables, thereby restricting airflow. A clear out of these spaces is advised.
  • Implement hot and cold aisles. This is one of the most obvious best practises. Gartner says traditional datacentres use a "classroom style" to position their racks, whereby all the intakes face in one direction. The problem with this setup is that hot air exhausted from one row, mixes with cold air being drawn into the adjacent row, thereby increasing cold-air supply temperature in uneven ways. Newer rack layout practises over the last ten years instead organise rows into hot and cold aisles, which offering much better control of air flow.
  • Install sensors. Seems obvious, but how do you tell if you have a temperature problem in a certain area of your datacentre? Gartner says a minimal investment in this technology could reap big insights into datacentre operations and can also provide a method for analysing the results of improvements made to the cooling systems.

Jump to page : [ 1 ] [ 2 ]

Follow highlights from ComputerworldUK on Twitter
Sign up for our Daily Newsletter
The UK IT News widget Get it for your site!

« prev article | more best practice news | next article »

Advert

close

Email this article to a friend or colleague:




PLEASE NOTE: Your name is used only to let the recipient know who sent the story, and in case of transmission error. Both your name and the recipient's name and address will not be used for any other purpose.

close
  • This article is now being printed.
close

What are your views on this subject? Use the form below to post a comment on this article up to 1000 characters.


Characters remaining:

close

Click below to add 'Gartner spells out route to datacentre efficiency - Best practice - ComputerworldUK' to your blog.



If you do not have a ComputerworldUK Account and would like to use this feature, please Register.

If you are a registered, logged-in user, this will post the title and first paragraph of this story to your blog to share with your readers.

What is this?

Advert

WHITE PAPERS

  • Legal risks: Employee use of the internet and email
    Exploring the challenges facing IT Mangers today and vital steps to ensure safe internet an email use by employees.
  • Phishing for victims
    This White Paper examines the phenomenon of phishing. It explains the potentially catastrophic threat it presents to all kinds of organisation. Exploding some widespread myths, it lights up the murky waters where phishing first emerged and where it continues to evolve. But it also highlights what your business can do to blunt the threat.
  • Challenges and opportunities of PCI
    The control framework implicit in the Payment Card Industry Data Security Standard (PCI DSS) provides an enterprise structure for improving operational, security, and audit performance.
  • Social CRM comes of age
    Who is this “social customer”? What strategies and tools does the new breed of CRM provide to do something about this?
  • Risk Management: Protect and Maximize Stakeholder Value
    What has held organisations back from a broader adoption of risk management programs?
*